Team builds affordable zero energy home - zero energy home
Fortified Gold requires an engineered continuous load path from the roof all the way to the foundation.

When the team at Addison Homes in Greenville, SC began the “Attainable Zero” project, the goal was to construct a small, high-performance home that a middle-class family could realistically afford. The team aimed to meet the Department of Energy’s Efficient New Home program requirements while also pursuing Fortified Gold certification from the Insurance Institute for Business and Home Safety for resilience. The house needed to be all-electric with excellent indoor air quality, solar electricity generation, and battery storage, all while avoiding a luxury price tag on the roughly 1,150-square-foot design.

Building Affordable Zero Energy

Now that the project is complete, the basic premise held up. The team built the intended house and remained on budget, aside from unforeseen site work. This outcome reinforced a core lesson in high-performance construction: individual products and specifications matter, but the real work involves making all those elements function as a system. Sometimes these elements complement one another; other times, they collide. A detail that looks straightforward on paper can create a problem in the field.

The foundation presented one such collision of goals. The building lot had a gentle slope, so the team initially considered a stepped foundation with an encapsulated crawlspace. To reduce costs, they chose an insulated slab on a stem wall. This required compacting fill inside the stem wall before pouring the slab, which proved less expensive than detailing an encapsulated crawlspace. While sound, this choice led to an unintended consequence.

The team’s typical slab detail uses 1 inch of rigid foam at the perimeter and beneath the slab. For the Attainable Zero home, they increased this to 2 inches to improve thermal performance. The insulation turns vertically at the slab perimeter and ends up beneath a portion of the framed wall’s bottom plate. Thermally, this was fine. Structurally, it almost created a problem.

Fortified Gold requires an engineered continuous load path from the roof all the way to the foundation. The wall-to-foundation connection must meet a prescribed uplift resistance. However, 2 inches of the area beneath the plate was foam, and the team could not anchor the house to that. With normal 1-inch insulation, there is plenty of room for the connection. With 2 inches, it was tight enough to make the team question whether they had designed themselves into a corner.

The engineer ran the calculations to confirm the team could anchor the plate using Simpson Strong-Tie Titan anchors on both edges of the plate on each side of the thicker insulation. In practical terms, this meant using roughly twice as many connectors. It was workable but not ideal. The team documented the engineer’s prescribed connections with location-stamped photos for the Fortified third-party evaluator who verified the connection details.

The lesson was not that 2 inches of perimeter insulation was a mistake. It was that two good goals can intersect in an unfriendly way. The team was pushing for better energy performance at the exact location where they needed greater structural resilience. On the next project, this intersection gets resolved in design instead of in the field.

Wall Assembly and Roof Details

While the foundation details required careful coordination, the wall assembly was relatively familiar territory. The team almost always chooses 2×6 framing with continuous insulation on the exterior. They also specified triple-pane windows and sliding glass doors. These choices provided excellent efficiency at a reasonable cost-benefit ratio. The glazing was particularly important because this is a small house with a relatively large amount of glass. The team wanted the best-performing units they could reasonably fit into the budget.

At the roof, the team changed course from their original thinking. Early on, they looked at installing continuous insulation above the roof deck. Once they worked through the structural requirements to meet Fortified Gold requirements and the cost of correctly installing continuous insulation on the roof without compromising the edge details required to eliminate the peel risk to the roofing in a high-wind event, they could not find an easy way to make that approach work without adding substantial complexity and cost.

The team ultimately insulated the underside of the roof deck with open-cell spray foam. Spray foam isn’t always the first choice, but in this case, it allowed the ductwork to remain inside the conditioned space. In the market, spray-foam installers commonly install about 5 inches of open-cell foam at a roof deck, or roughly R-19. The team insisted on R-30, which required about 8 inches. Every time they do this, it leads to a discussion. The installer points out that the rest of the enclosure exceeds code and the foam can be installed at a lower R-value than the prescriptive code using the alternative UA compliance path. While technically true, it isn’t the way they want to build.

Better windows or walls aren’t an excuse to intentionally weaken another part of the enclosure. For this assembly, R-30 also represents a reasonable point of diminishing returns. Going significantly beyond it would require additional foam passes and considerably more expense. If they were insulating a conventional attic with blown insulation, they would typically install R-44 to R-49. With the spray foam, they are getting both the insulation and the air-sealing benefit while keeping the mechanical systems within the enclosure.

Systems and Indoor Environment

Once the enclosure was substantially complete, the builders performed repeated air-leakage testing. They even used a smoke machine to track down some of the small air leaks that are difficult to find by visual inspection alone. One thing this project reinforced is that getting a very small house extremely tight can be harder than people expect. That is because a small house does not necessarily have proportionally fewer penetrations.

The 1,200-square-foot home has four exterior doors. The builder is currently constructing a 6,000-square-foot house that also has four exterior doors. Both houses still have bottom plates, top plates, windows, plumbing and electrical penetrations, and all the other transitions that can leak. In the smaller house, those potential leakage points represent a much larger percentage of the enclosure, and the leakage is being measured against a much smaller volume of air. That means every detail matters.

The builders’ initial testing occurred before drywall was complete, which they used to guide their air sealing strategy. The final blower test conducted at the very end of the job came in at exactly 1 ACH50, exactly where they wanted it to be. This is also why airtightness cannot simply be assigned to the insulation contractor. Rather, it is a construction-management issue. The builders must know where their air barrier is, communicate that to every trade, and test while they can still address any problem areas. Finding a leak after the finishes have been installed is a very different proposition from finding it while the framing is open.

Mechanical Systems and Indoor Air

A tight enclosure changes the way one thinks about mechanical systems. Once one intentionally eliminates uncontrolled air leakage, one must also intentionally manage temperature, humidity, filtration, and fresh air. The approach on the project was to tackle each of these tasks with proven technologies and equipment: A variable-speed heat pump handles heating and cooling. A dedicated dehumidifier manages moisture.

An ERV supplies controlled fresh air, and a MERV-15 central filter at the air handler removes particulates. The builder likes thinking of those as separate functions. The heat pump’s job is temperature. The dehumidifier’s job is moisture removal. The ERV’s job is ventilation. The air filter’s job is removing particulates from the air. Together they create the indoor environment one wants in a controlled approach without depending on accidental leakage through the building enclosure.

Electrification and Maintenance

There is a homeowner responsibility that comes with this. There really isn’t such a thing as a completely maintenance-free high-performance house if one cares about healthy indoor air, efficiency, and moisture control. The homeowner will have several filters that need periodic attention. Delivering a high-performance house includes making sure the owners understand what the systems do and why that maintenance matters. However, because the home is built to a higher performance level of air tightness, each piece of equipment will have to work less to keep the conditioned environment comfortable, dry, and healthy. Lower fan speeds and fewer heating and cooling cycles shrinks energy use, and reduces wear and tear on equipment, and extends the life of filters.

Electrification and Resiliency

At Addison Homes, the team committed to encouraging clients to build all-electric homes. For the family that owns this home, this was not only a comfortable choice, it was the preferred choice. Cooking is by induction. The team is still finalizing some of the other appliances, including a heat-pump clothes dryer. The benefit of having no combustion equipment plays well into the indoor air quality but also supports the overall resiliency strategy for the home. The solar shingles are installed, and the house has battery storage. This system ties into the electric car charger that is controlled by the smart electric panel to optimize battery life.

Onsite power generation not only helps reduce overall energy use; it also is a key component to address resiliency in the storm-prone region. A rough estimation is that the battery could support the house for around 24 hours during an outage, but actual runtime will depend heavily on what loads are operating and whether the solar array is producing power during the outage. During daylight hours, the solar can help serve the house while recharging the battery, which changes the equation considerably.

The energy transfer equipment includes a quick-connect that will allow a generator to be added later if the homeowners decide they need longer-duration backup. This provides added flexibility while still keeping the initial cost of construction within budget. The team’s approach in this area is that resilience does not necessarily mean installing every possible backup system on day one. It can also mean leaving a straightforward path for future needs.